What is dust collector & how timer Board Interfaces it ?
The pulse jet design have group of bags enclosed in housing. Dirty air enters the housing and travels through the filter bags. Filtered air is vented to the atmosphere. High pressure (4-6 kg/sq cm) air pulse dislodges the dust, which falls into the hopper for disposal or recovered for use. Cleaning cycle is initiated from remote timer (Continuous Cycle) or pressure switch (on demand pulsing) Signal actuates diaphragm solenoid valves which permits momentary jet of high pressure air to each venturi and filter bag. Only one row of bags is cleaned at pre-selected intervals, while the system is in operation.

 
     
 
Timer Board Operating Modes....
Continuous Cycle Mode :

The boards have two operating modes available for different applications. Starting with the most vital mode, it is capable of operating in a continuous cleaning cycle. This can be started by putting a jumper (shorting link) between the pressure switch input to the terminal strip connection. Two setup parameters control operation: off time, on time. on Time and off time specifically deal with the solenoid on time and the time interval between the end of the on pulse and the start of the next.

   
On Demand Mode (Air save mode) :

Demand mode operation can be configured using the high limit and low limit inputs. A simple on-off system can be setup with a single pressure switch connected to the high limit input. Better control can be achieved with a high and low limit switch set such as is provided in the Photohelic® (DWYER Make) pressure gage. In this on demand mode, on time and off time may be programmed to define the cleaning cycle. Meaning there by Pulsing will start when DP (Delta "P") is high & continue till it reaches low set point.

   
No. of Channels Selection :

A jumper (Flying lead wire) connector is provided to select the last channel used. Place the jumper on the pins corresponding to the last channel to be used in the Operation .

   
Off Time and On Time Setup :

Off Time defines the period of time between solenoid activations when no channels are enabled. This value may be set between 2 second and 120 seconds. On Time defines the solenoid Firing time. The value may be set between 20 m/sec and 200 m/sec . If adjustments are made while the system is in operation, the new setting will take effect in the following next Channel solenoid operation. Do not use excessive force to rotate the potentiometers. This will damage the Timer unit.

 
     
 

Timer cards
The use of micro controllers in in bag house sequencers has seen a change in emphasis from unit cost considerations alone back towards emission performance & bag house maintenances. This recent change has been brought about by several factors including better automation provisions, dust collection accountability / process reporting as well as fulfillments of certification requirements.
A small, but vital, item of Bag House equipment. controls the sequencing of solenoid valves. The duration of the Valve opening can be varied between 20 -200 milliseconds, and the time interval between the activation is adjustable from 2- 60 Seconds. The controllers are micro controller design, developed over a number of years through extensive and exacting site testing All controllers are fully (100%) tested before being sent to site and they have been proved reliable over the whole field of dust control applications. Only the best quality electronic components are used, so that the reliability of the whole is to a very high standard Consequently on site failures all which have occurred within first week of operation are less than 0. 5 %.

 
     
 
     
Atmel 89C2051 micro controller
Compact design
Low Cost -Ex stock available

Sheet metal Housing [Only Board also available]

Manual Pulsing To test Timer
UL Listed
Model :MPS1-WD5#1
5 output timer board
5 output timer board in NEMA box
     
     
   
     
Atmel 89C2051 micro controller
Compact design
Low Cost -Ex stock Available
Manual Pulsing To test Timer
UL Listed
Available in NEMA box
Model : MPS1-WD9#2
10 output timer board
10 output timer board in NEMA box
 
     
     
   
     
Atmel 89S52 micro controller
UL listed
Manual Pulsing To Test Board
Available in NEMA box
Low Cost-Ex stock available
Model : MPS1-WD15#2
Built In zero speed Possible (Optional extra)
15 output timer board 15 output timer board in NEMA box
 
     
     
   
     
Atmel 89S52 micro controller
UL listed
Manual Pulsing To Test Board
Available in NEMA box
Low Cost-Ex stock available
Model : MPS1-WD20#2
Built In zero speed Possible (extra cost)
Remote / Local wiring possible (extra cost)
Cascading possible
20 output timer board In 20 output timer board in NEMA box
 
     
     
   
     
Atmel 89S52 micro controller
UL listed
Manual Pulsing To Test Board
Available in NEMA box
Low Cost-Ex stock available
Model : MPS1-WD25#2
Built In zero speed Possible (Optional extra)
Remote / Local wiring possible (extra cost)
25 output timer board 25 output timer in NEMA box  
     
     
   
     
CMOS Integrated Circuits
Low cost Model : WD VIII ver1.0
Zero Crossing Firing
Board Size 200 x 215 mm
Interval Time adjustable from 2- 180 Seconds
well-made & very proven design
24 VDC model also available (at extra cost)

Remote / Local wiring possible (extra cost)

10 output timer board    
 
     
  Timer Boards STANDARD :  
 
Listing : Yes
Power : 230v / 110v, 50 / 60Hz
Pulse freq. : 2-120 sec (int. time) [Different Timings On request]
Pulse Duration : 20-200 m sec. [Different Timings On request]
Output Glands : PG 9 for solenoids--- Input Glands : PG13.5 for power
On Demand Pulsing : Standard on all models
Red Clock Led : Yes Power On Led : Yes
Feed back relay : Yes
Sequence Function Indicators Leds : Yes
Manual Pulsing for Testing : Yes
Conformal Coat: Yes (Loctite)
 
     
  Significant Features of all Timer Boards ....  
 
Ex-stock Available Timer Boards 5, 10, 15, 20 outputs
Delivery with in 48 hrs for Quantities up to 25 Boards
Proven product for last 20 years
Excellent performance, Extremely low failure rates
100% testing of all Sequential Timers On Simulated Air Headers with all types of Famous make Solenoids
 
     
  Pricing : See Price List  
     
  Click to See here Terms & Conditions of sale , International sale Terms & Conditions of sale